Water hammer is a sudden pressure surge in plumbing when flowing water is abruptly stopped — for example, when a solenoid valve closes, a washing machine finishes filling, or a toilet shuts off. This surge travels back through piping and can cause:
The longer the run and the faster the water velocity, the greater the force exerted on the pipes, sometimes exceeding static pressure. The last 15% of the valve closure is directly related to the intensity of the increase in pressure.
Without mitigation:
Older DIY air chambers (simple capped pipes) were common but lost air quickly, becoming ineffective. Modern pre-manufactured water hammer arrestors with sealed gas chambers are required. The resulting pressure developed in the water distribution system will be approximately 60 times the normal pressure.
Formula: Water hammer shock (PSI)= Flow velocity (ft/sec) X 60
This means:
The Code identifies water hammer as a pressure buildup that should be prevented wherever valves and faucets exist, especially at the end of long runs. It explicitly allows either:
Air chambers must be:
Types of water hammer arrestors:
Modern arrestors use a sealed chamber with a piston or diaphragm that:
Device Standard
Water hammer arrestors shall conform to ANSI/ASSE 1010 in accordance with NPC 2.2.10.15. (1).
Location & Quantity
Install arrestors:
Larger branches with multiple fixtures may require multiple devices to absorb energy adequately. Plumbing design must consider fixture unit loads and flow rates.


Note: When water pressure in the line exceeds 65 psi, upsize to the next sized water hammer arrestor. All information provided is based on 10 feet per second or less.
While water hammer arrestors are not part of conditioning in the same way as water filters or softeners, they integrate into the domestic water distribution:
They are not part of water treatment systems but protect the system following conditioning, softeners, filters, etc.
Inspect arrestors if system noise returns; failed arrestors may need to be replaced.

If the velocity of the water in a piping system were 30 feet per second, what would the resulting water hammer pressure be?
30 (ft/sec) X 60= 1800 PSI
Example Layout (Branch Line Longer Than 20 ft)
Primary arrestor — near the quick-closing valve
Secondary arrestor — mid-run of the branch
If the branch has 20 fixtures, for example, the placement of the water hammer arrestor is as follows:
The 1st water-hammer arrestor is located between the last fixture and the second-to-last fixture on the branch. The 2nd water-hammer arrestor is located halfway along the fixtures. In this scenario, outlined with 20 fixtures, the second arrestor would be located between the 10th and 11th fixture. Both water hammer arrestors would be size “B.”
A commercial building has three flushometer water closets connected to a 1″ branch line that is 12 m long from the main distribution pipe. Each flushometer valve is a quick-closing device. Loud hammering occurs when the valves close.
According to the National Plumbing Code, what is the correct method to control water hammer in this installation?
A. Install one water hammer arrestor at the water meter
B. Install a minimum of 2 water hammer arrestors on the branch line serving the flushometer valves
C. Install expansion tanks near the flushometer valves to absorb shock
D. Install only 1 water hammer arrestor on the branch line serving the flushometer valves
B — Install water hammer arrestors on the branch line serving the flushometer valves
2.6.1.6. Water Hammer
Water distribution systems shall be designed and installed to prevent excessive water hammer.
Quick-closing valves present
Long branch line
Hammer occurring
Protection required
Flushometer valves:
These are among the most common exam examples that require arrestors.
Because the branch is long (12 m = 39.36 ft):
Good practice (and exam expectation):
This satisfies the intent of:
NPC 2.6.1.6 — prevent excessive water hammer
A — Arrestor at the meter
Too far from quick-closing valves
Does not control local shock
C — Install expansion tanks near the flushometer valves to absorb shock
Does not eliminate hammer, only good for thermal expansion.
D — Install only 1 water hammer arrestor on the branch line serving the flushometer valves
Branch is longer than 20 feet which require additional arrestors.
Download now to access 500+ practice questions and master the Red Seal Plumbing!