Understanding general lighting load calculations is crucial for electrical professionals. These calculations determine the minimum electrical capacity required for a dwelling's lighting and general-use receptacles. Accurate calculations ensure safe and adequate power distribution, preventing overloads and potential hazards. This topic frequently appears on NEC electrical exams, making it essential for aspiring electricians, contractors, and electrical engineers to master.

Example General Lighting Load Questions on NEC Electrical Exams

Calculate the demand load, in VA, on the ungrounded service-entrance conductors for the general lighting and receptacle loads in a two-family dwelling to be constructed, given the following information: • 3,500 square feet of livable space per unit • 800 square foot shared garage • 300 square foot shared covered patio • 1,500 square foot unfinished basement (planned for future use) • Two (2) small-appliance branch circuits and one (1) branch circuit for the laundry room per unit
Calculate the general lighting load for a 4,200 square foot single-family home with three small appliance branch circuits and one laundry circuit. What is the total demand load in VA?
A triplex has 2,000 square feet of living space per unit. Each unit has two small appliance branch circuits and one laundry circuit. What is the combined general lighting load for all three units in VA?

How to Identify a General Lighting Load Question on NEC Electrical Exams

Key phrases to look out for in the general lighting load question:

  • "General lighting load"
  • "Demand load for lighting and receptacles"
  • "Square footage" or "livable space"
  • "Small appliance branch circuits"
  • "Laundry circuit"

When you spot these elements:

  • Confirm it's a general lighting load question, not a specific circuit or appliance load question
  • Refer to NEC sections 220.5, 220.41, 220.45, and 220.52

General Lighting Load Articles: NEC 220.5, 220.41, 220.45, 220.52

To correctly apply NEC Articles 220.5, 220.41, 220.45, and 220.52, focus on these main elements:

  1. General Lighting Load (220.41): 3 VA per square foot for dwelling units
  2. Demand Factors (220.45): Apply demand factors to the calculated load
  3. Small Appliance and Laundry Loads (220.52): Include these in the calculation

Summary of how to use the codebook:

  1. Use Section 220.12 to determine the unit load per square foot (3 VA for dwellings)
  2. Apply Table 220.45 for demand factors
  3. Add loads for small appliance and laundry circuits as per 220.52

Walkthrough for a NEC Electrical Exam General Lighting Load Question

Question: Calculate the demand load, in VA, on the ungrounded service-entrance conductors for the general lighting and receptacle loads in a two-family dwelling to be constructed, given the following information:

  • 3,500 square feet of livable space per unit
  • 800 square foot shared garage
  • 300 square foot shared covered patio
  • 1,500 square foot unfinished basement (planned for future use)
  • Two (2) small-appliance branch circuits and one (1) branch circuit for the laundry room per unit

Step 1: Determine the total square footage using Section 220.5(C)

  • Include livable space for both units and unfinished basement (planned for future use)
  • (3,500 sq. ft. x 2) + 1,500 sq. ft. + 800 sq. ft. = 9,300 sq. ft.
  • Note: Garage sq. footage must be included in unit load calculation beginning with 2023 NEC code cycle
  • Note: Covered patio is not included in this calculation

Step 2: Calculate the general lighting load

  • Multiply total square footage by 3 VA/sq. ft.
  • 9,300 sq. ft. x 3 VA/sq. ft. = 27,900 VA

Step 3: Add small appliance and laundry circuit loads (for both units) using 220.52

  • Four small appliance circuits: 4 x 1,500 VA = 6,000 VA
  • Two laundry circuits: 2 x 1,500 VA = 3,000 VA
  • Total additional load: 6,000 VA + 3,000 VA = 9,000 VA

Step 4: Calculate total connected load

  • General lighting load + Small appliance and laundry loads
  • 27,900 VA + 9,000 VA = 36,900 VA

Step 5: Apply demand factors (NEC 220.42)

  • First 3,000 VA at 100%: 3,000 VA
  • Remaining load (36,900 VA - 3,000 VA = 33,900 VA) at 35%: 33,900 VA x 0.35 = 11,865 VA

Step 6: Calculate final demand load

  • Sum of demand factors: 3,000 VA + 11,865 VA = 14,865 VA

Therefore, the demand load on the ungrounded service-entrance conductors for the general lighting and receptacle loads is 14,865 VA.

Want to pass your electrical licensing exam on the first try?

Download now to access 3,000+ practice questions and master the NEC Code!

student passing their exam using dakota prep