The Washington State Journeyman Electrician exam is one of the most challenging in the country, requiring 8,000 verified hours of supervised electrical work and 96 hours of classroom instruction before you’re even eligible. Candidates with military training or out-of-state licenses may also qualify, provided they meet Washington’s work-hour and documentation requirements. Passing the exam earns your state-issued Journeyman Electrician Certificate, an essential step for advancing your electrical career.
The exam is divided into two parts: 60 questions on the National Electrical Code® (NEC) and electrical theory (3 hours) and 17 questions on Washington State laws and rules (1 hour). To succeed, you must score at least 70% overall. Expect questions on grounding, wiring methods, conductor sizing, overcurrent protection, motors, special occupancies, and local RCW 19.28 and WAC 296-46B requirements. Because the test combines national code with Washington-specific regulations, being able to navigate both references quickly is key.
Dakota Prep gives you the edge with practice exams built for the Washington journeyman test, including 3,000+ NEC-aligned practice questions. Learn to navigate the 2020 NEC efficiently, master Washington’s laws, and sharpen your calculation skills under timed conditions. Start today with a free Washington journeyman electrician practice exam and build the confidence to pass on your first attempt.
The correct answer is
NEC 2017: Table 310.15(B)(3)(a)
NEC 2020: Table 310.15(C)(1)
NEC 2023: Table 310.15(C)(1)
That's correct! Way to go
NEC 2017: Table 310.15(B)(3)(a)
NEC 2020: Table 310.15(C)(1)
NEC 2023: Table 310.15(C)(1)
The correct answer is
NEC 2017: 680.32
NEC 2020: 680.32
NEC 2023: 680.32
That's correct! Way to go
NEC 2017: 680.32
NEC 2020: 680.32
NEC 2023: 680.32
The correct answer is
NEC 2017: 430.109(D)(3)
NEC 2020: 430.109(D)(3)
NEC 2023: 430.109(D)(3)
Step 1: Verify that 30 hp is within the specified range of over 2 hp up to and including 100 hp.
Step 2: Review the three provisions, focusing on provision (3).
Step 3: Identify that the code specifies "not more than 150 percent of the motor full-load current" for the rating or setting of separate fuses or an inverse time circuit breaker.
Step 4: Confirm that 150% is the correct percentage stated in the code.
That's correct! Way to go
NEC 2017: 430.109(D)(3)
NEC 2020: 430.109(D)(3)
NEC 2023: 430.109(D)(3)
Step 1: Verify that 30 hp is within the specified range of over 2 hp up to and including 100 hp.
Step 2: Review the three provisions, focusing on provision (3).
Step 3: Identify that the code specifies "not more than 150 percent of the motor full-load current" for the rating or setting of separate fuses or an inverse time circuit breaker.
Step 4: Confirm that 150% is the correct percentage stated in the code.
The correct answer is
NEC 2017: 210.11(C)(1) & (2), 220.52(A) & (B)
NEC 2020: 210.11(C)(1) & (2), 220.52(A) & (B)
NEC 2023: 210.11(C)(1) & (2), 220.52(A) & (B)
2-small appliance circuits @ 1,500 VA each = 3,000 VA1-laundry circuit @ 1,500 VA each = 1,500 VATotal = 4,500 VA
That's correct! Way to go
NEC 2017: 210.11(C)(1) & (2), 220.52(A) & (B)
NEC 2020: 210.11(C)(1) & (2), 220.52(A) & (B)
NEC 2023: 210.11(C)(1) & (2), 220.52(A) & (B)
2-small appliance circuits @ 1,500 VA each = 3,000 VA1-laundry circuit @ 1,500 VA each = 1,500 VATotal = 4,500 VA
The correct answer is
NEC 2017: Table 250.66, 250.66(B)
NEC 2020: Table 250.66, 250.66(B)
NEC 2023: Table 250.66, 250.66(B)
That's correct! Way to go
NEC 2017: Table 250.66, 250.66(B)
NEC 2020: Table 250.66, 250.66(B)
NEC 2023: Table 250.66, 250.66(B)
The correct answer is
NEC 2017: Chapter 9, Table 4
NEC 2020: Chapter 9, Table 4
NEC 2023: Chapter 9, Table 4
Step 1: Find the maximum area for conductors within the conduit
Maximum percent of area of Trade size 1 1/2 (41) EMT conduit that can be used for conductor fill = 40 percent; Chapter 9 Table 1
Cross-sectional Area of 41 EMT conduit at 40 percent = 0.814 in² (526 mm²); Chapter 9 Article 358
Step 2: Find the area of a single No. 10 AWG XHHW conductorCross-sectional Area of No. 10 AWG XHHW = 0.0243 in² (15.68 mm²); Chapter 9 Table 5
Step 3: Calculate the maximum number of conductors
Maximum number of conductors = 0.814 in² / 0.0243 in² = 33.49
That's correct! Way to go
NEC 2017: Chapter 9, Table 4
NEC 2020: Chapter 9, Table 4
NEC 2023: Chapter 9, Table 4
Step 1: Find the maximum area for conductors within the conduit
Maximum percent of area of Trade size 1 1/2 (41) EMT conduit that can be used for conductor fill = 40 percent; Chapter 9 Table 1
Cross-sectional Area of 41 EMT conduit at 40 percent = 0.814 in² (526 mm²); Chapter 9 Article 358
Step 2: Find the area of a single No. 10 AWG XHHW conductorCross-sectional Area of No. 10 AWG XHHW = 0.0243 in² (15.68 mm²); Chapter 9 Table 5
Step 3: Calculate the maximum number of conductors
Maximum number of conductors = 0.814 in² / 0.0243 in² = 33.49
The correct answer is
NEC 2017: 210.12(A)
NEC 2020: 210.12(A)
NEC 2023: 210.12(A)
That's correct! Way to go
NEC 2017: 210.12(A)
NEC 2020: 210.12(A)
NEC 2023: 210.12(A)
The correct answer is
NEC 2017: Table 314.16(B), 314.16(B)(4)
NEC 2020: Table 314.16(B), 314.16(B)(4)
NEC 2023: Table 314.16(B), 314.16(B)(4)
Step 1: Determine box capacity
Calculate how many individual #12 wires the box can hold:
Box volume ÷ Volume per #12 wire = Total wire capacity
18 cu. in. ÷ 2.25 cu. in. = 8 wires
Step 2: Account for device
Subtract the wires used by the duplex receptacle.
314.16(B)(4) states that a double volume allowance on the largest conductor connected to the device
Total wire capacity - Device wires = Remaining wire capacity
8 wires - 2 wires = 6 wires
Step 3: Identify cable composition
Note the number of wires in each 12/2 NM cable:
12/2 with ground NM cable contains 3 wires where 1 is grounding
Step 4: Calculate grounding allowance
Up to four equipment grounding conductors enter a box, a single volume allowance shall be made based on the largest equipment grounding conductor entering the box.
6 wires - 1 wires = 5 wires
Step 5: Calculate conductor allowance
Divide remaining capacity by conductors per cable:
Remaining wire capacity ÷ conductors per cable = Number of cables allowed
5 wires ÷ 2 wires = 2.5 cables -> 2 cables
That's correct! Way to go
NEC 2017: Table 314.16(B), 314.16(B)(4)
NEC 2020: Table 314.16(B), 314.16(B)(4)
NEC 2023: Table 314.16(B), 314.16(B)(4)
Step 1: Determine box capacity
Calculate how many individual #12 wires the box can hold:
Box volume ÷ Volume per #12 wire = Total wire capacity
18 cu. in. ÷ 2.25 cu. in. = 8 wires
Step 2: Account for device
Subtract the wires used by the duplex receptacle.
314.16(B)(4) states that a double volume allowance on the largest conductor connected to the device
Total wire capacity - Device wires = Remaining wire capacity
8 wires - 2 wires = 6 wires
Step 3: Identify cable composition
Note the number of wires in each 12/2 NM cable:
12/2 with ground NM cable contains 3 wires where 1 is grounding
Step 4: Calculate grounding allowance
Up to four equipment grounding conductors enter a box, a single volume allowance shall be made based on the largest equipment grounding conductor entering the box.
6 wires - 1 wires = 5 wires
Step 5: Calculate conductor allowance
Divide remaining capacity by conductors per cable:
Remaining wire capacity ÷ conductors per cable = Number of cables allowed
5 wires ÷ 2 wires = 2.5 cables -> 2 cables
The correct answer is
NEC 2017: 690.31(G)
NEC 2020: 690.31(B)
NEC 2023: 690.31(B)
That's correct! Way to go
NEC 2017: 690.31(G)
NEC 2020: 690.31(B)
NEC 2023: 690.31(B)
The correct answer is
NEC 2017: Table 430.250, 430.52(C)(1), 430.52(C)(1)(a)(2), 240.6
NEC 2020: Table 430.250, 430.52(C)(1), 430.52(C)(1)(a)(2), 240.6
NEC 2023: Table 430.250, 430.52(C)(1), 430.52(C)(1)(a)(2), 240.6
Step 1: Find the FLC for a 20 hp, 208-volt, three-phase Design B motor in Table 430.250. The FLC is 59.4 amperes.
Step 2: Calculate 225% of FLC: 59.4 × 225% = 133.65 amperes.
Step 3: The next lower standard fuse size is 125 amperes, which doesn't exceed 225% of FLC.
Step 4: Therefore, the maximum permitted fuse rating is 125 amperes.
That's correct! Way to go
NEC 2017: Table 430.250, 430.52(C)(1), 430.52(C)(1)(a)(2), 240.6
NEC 2020: Table 430.250, 430.52(C)(1), 430.52(C)(1)(a)(2), 240.6
NEC 2023: Table 430.250, 430.52(C)(1), 430.52(C)(1)(a)(2), 240.6
Step 1: Find the FLC for a 20 hp, 208-volt, three-phase Design B motor in Table 430.250. The FLC is 59.4 amperes.
Step 2: Calculate 225% of FLC: 59.4 × 225% = 133.65 amperes.
Step 3: The next lower standard fuse size is 125 amperes, which doesn't exceed 225% of FLC.
Step 4: Therefore, the maximum permitted fuse rating is 125 amperes.