Transformer conductor sizing questions are common on electrical licensing exams because they test multiple concepts: load calculations, continuous load factors, and conductor ampacity selection. Understanding how to handle different transformer configurations (single-phase, three-phase, and multiple transformers) is crucial for passing your exam.
Example Transformer Conductor Sizing Questions on NEC Electrical Exams
What is the minimum size THWN insulated copper conductors permitted to feed a 3Ø transformer bank consisting of three 30 kVA, 480-120/240 V single-phase transformers if the transformer were protected by the maximum allowable overcurrent device?
A 225 kVA, dry-type, 480-208/120 V transformer primary must be fed with minimum __________ THW copper conductors where the transformer terminations are rated at 167°F if the transformer were protected by the maximum allowable overcurrent device.
An office building uses a 75 kVA, 3-phase, 600-208Y/120 V transformer terminating at 167°F (75°C). What are the minimum size RHW insulated copper conductors permitted to feed the primary of the transformer if the maximum allowable rated overcurrent protection is used.
How to Identify a Transformer Conductor Sizing Question on NEC Electrical Exams
Key phrases to look out for:
- "Transformer primary/secondary conductors"
- "Minimum conductor size"
- "Full load current"
- "kVA rating"
- "Transformer bank"
- References to Article 450
- Temperature ratings
When you spot these elements:
- Identify transformer configuration (single-phase, three-phase, or bank)
- Note the kVA rating(s)
- Check voltage ratings
- Refer to NEC Articles 450 and 310.16
Transformer Conductor Sizing Articles: NEC 450 and 310.16
To correctly size transformer conductors, focus on these main elements:
Basic Calculations:
- Single-phase: I = VA ÷ V
- Three-phase: I = VA ÷ (√3 × V)
Configuration Considerations:
- Individual transformers vs. transformer banks
- Are the secondary conductors considered protected by the primary OCPD?
- Temperature ratings and derating factors
Special Requirements:
- Overcurrent protection
- Transformer termination temperature ratings
- Ambient temperature corrections
Different Transformer Configurations and Their Calculations
Single-Phase Transformers
- Formula: I = VA ÷ V
- Example: 50 kVA, 480V primary
- I = 50,000 ÷ 480 = 104.17A
Three-Phase Transformers
- Formula: I = VA ÷ (√3 × VLine)
- Example: 75 kVA, 480V primary
- I = 75,000 ÷ (1.732 × 480) = 90.32A
Multiple Transformer Banks
- Calculate total kVA first
- Example: Three 25 kVA transformers
- Total kVA = 3 × 25 = 75 kVA
- Then use appropriate formula based on configuration
Key Differences Between Primary and Secondary Calculations:
- Voltage: Use the specific voltage for the side you're calculating
- Primary: Higher voltage (600V in this case)
- Secondary: Lower voltage (208V in this case)
- Current: Inversely proportional to voltage
- Higher voltage = Lower current
- Lower voltage = Higher current
- Conductor Size: Usually larger on secondary side due to higher current
- Primary: Smaller conductor size typically needed
- Secondary: Larger conductor size typically needed
Walkthrough for NEC Electrical Exam Transformer Questions
Three-Phase Bank Question
What is the minimum permissible size of THWN insulated copper conductors permitted to feed a 3Ø transformer bank consisting of three 30 kVA, 480-120/240 V single-phase transformers if the transformer were protected by the maximum allowable overcurrent device?
Step 1: Calculate Total kVA and Full Load Current
- Total kVA = 3 × 30 kVA = 90 kVA
- Primary voltage = 480V three-phase
- I = 90,000 ÷ (√3 × 480)
- I = 90,000 ÷ 831.4
- I = 108.38 amperes
Step 2: Find maximum allowable overcurrent protective device.
- Find maximum permitted primary overcurrent protection size
- Because the transformer configuration is not a 3-wire delta-delta, secondary overcurrent protection is required
- Maximum ampacity = 108.38 x 250% = 270.95 amperes NEC Table 450.3(B)
- Next LOWER standard rating for OCPD from Table 240.6(A) = 250 ampere OCPD
Step 3: Select Conductor Size Based off OCPD Rating
- Use Table 310.16 for THWN copper at 75°C
- Need ampacity > 250A
- 250 kcmil is rated 255A
- This is the minimum size that meets requirements
The minimum conductor size required is 250 kcmil copper.
Single Three-Phase Transformer Question
A 225 kVA, dry-type, 480-208/120 V transformer primary must be fed with a minimum __________ THW copper conductors where the transformer terminations are rated at 167°F if the transformer were protected by the maximum allowable overcurrent device.
Step 1: Calculate Full Load Current
- kVA = 225
- Primary voltage = 480V three-phase
- I = 225,000 ÷ (√3 × 480)
- I = 225,000 ÷ 831.4
- I = 270.95 amperes
Step 2: Find maximum size OCPD Maximum ampacity = 270.95 × 250%
- Minimum ampacity = 667.375 amperes
- OCPD maximum standard size = 600 amps
Step 3: Select Conductor Size
- Use Table 310.16 for THW copper
- Need ampacity > 600A NEC 240.4
- 1500 kcmil is rated 625A although 900 kcmil could be used because 600 is the next higher standard amp rating per NEC 240.4(B)
- (2) sets of parallel 350 kcmil rated at 310 A a piece could also be used
- This is the smallest size that meets requirements
The minimum conductor size required is 900 kcmil copper or parallel 350 kcmil conductors.
Secondary Conductor Sizing Question
Question: An office building uses a 75 kVA, 3-phase, 600-208Y/120 V transformer terminating at 167°F (75°C). What are the minimum size RHW insulated copper conductors permitted to feed the primary of the transformer if the maximum allowable rated overcurrent protection is used?
Step 1: Calculate Full Load Current for Secondary Side
- kVA = 75
- Secondary voltage = 208V three-phase
- I = 75,000 ÷ (√3 × 208)
- I = 75,000 ÷ 360.18
- I = 208.42 amperes
Step 2: Select the maximum allowable OCPD Maximum ampacity = 208.42 × 2.5
- Minimum ampacity = 521.05 amperes
- Next lower standard size OCPD = 500 amperes per NEC Table 240.6(A)
Step 3: Select Conductor Size
- Use Table 310.16 for RHW copper at 75°C
- Need ampacity > 500A
- 900 kcmil is rated 520 amps although 700 kcmil could be used per 240.4(B)
- Parallel 250 kcmil conductors rated 255 amps a piece could also be used
- This is the smallest size that meets requirements
The minimum conductor size required is 700 kcmil copper or parallel 250 kcmil conductors.