Transformer secondary conductors are critical components of electrical systems that provide a safe path for current drawn by utilization equipment. These questions frequently appear on electrical licensing exams because proper sizing of transformer secondary conductors is essential for safety and code compliance. Understanding how to size these conductors is crucial for passing your exam.
Key phrases to look out for:
When you spot these elements:
Section 240.21 states…
“Overcurrent protection shall be provided in each ungrounded circuit conductor and shall be located at the point where the conductors receive their supply except as specified in 240.21(A) through (H)” with 240.21(C) pertaining to transformer secondary conductors.
240.21(C)(1) states that unless a transformer is 2-wire single-phase, or 3-wire delta-delta three-phase, they are not considered protected by the primary overcurrent device. In other words, in general, if a transformer has a neutral, we must have a breaker or fuses on the secondary of a transformer.
The tap rules located in Sections 240.21(C)(2)-(4) allow us to bypass this rule, but only under specific conditions.
So, typically we would need a breaker or fuse at the secondary terminals. The reason we almost never see this done is because of the tap rules found in Section 210.21(C)(2)-(4). Because a transformer creates a separately derived system, the secondary conductors are not considered protected by the breaker or fuses located on the primary side of the transformer.
These tap rules allow us to install our secondary conductors without their own overcurrent protection so long as we meet all of these conditions for the individual tap rules.
Question: A panelboard being protected with a 200 amp main breaker is being fed from the secondary of a 75 kVA 480V-208/120V transformer. What are the minimum size THWN insulated copper conductors permitted to feed the panelboard where the secondary conductors are 8 feet in length?
Step 1: Identify Key Information
Step 2: Locate and apply appropriate tap rule
Step 3: Select Conductor Size Using Table 310.16
Minimum size secondary conductor size = 3/0 AWG THWN
Question: For a commercial application, what are the minimum size copper THWN insulated conductors permitted to supply a load from the secondary of a 75 kVA 480V-208/120V transformer where secondary conductors are 15 feet in length and a 225 amp breaker is protecting the primary conductors.
Step 1: Identify Key Information
Step 2: Choose the appropriate secondary tap rule
Step 3: Calculate Minimum Ampacity Using Section 240.21(C)(6)
Step 4: Choose the minimum size conductor per Table 310.16
The minimum size copper branch-circuit conductors required are 2/0 AWG THWN.
Download now to access 3,000+ practice questions and master the NEC Code!