Voltage Drop: The Sneaky Energy Thief

Imagine electricity as a marathon runner carrying voltage from the panel to the load. Along the way, it gets tired running through long wires — that tiredness is called voltage drop.

Just like water loses pressure in a long pipe, voltage loses strength over distance. The longer or thinner the wire, the more it drops!

How Much Can It Drop?

According to CEC Rule 8-102:

  • Branch circuits: Max 3%
  • Total drop (feeder, through the panel, branch): Max 5%

Go beyond that, and your equipment might not work right—or at all. It's like giving a flashlight half-dead batteries 

The Voltage Drop Formula Team

Meet your formula friends:

  • V = Voltage at the source (in Volts)
  • VD = Voltage lost (drop) (in Volts)
  • K = Resistance per km (from Table D3)
  • f = System factor (1.73 for 3-phase, 2 for single-phase)
  • I = Current (amps)
  • L = Length of the wire (meters)

These characters team up to find either the voltage drop, the wire size, or how far the current can run!

How to Hunt Down the “K” Factor (Voltage Drop Style)

To figure out your K factor — the secret for voltage drop — you need four key ingredients. Just remember the acronym PICA (like a cool code name!):

P – Power Factor / How “resistive” is your load? (100% is a perfect heater, but motors usually vary.)

I – Installation Type / Are the wires in a Raceway or a Cable Tray? This affects resistance!

C – Conductor Size / What AWG size are you using? (Smaller number = thicker wire)

A – AC or DC / Voltage drop behaves differently for alternating vs. direct current.

Bonus Rule:

  • If you don’t know the power factor, no problem — just be safe and choose the highest resistance value from the table.
  • All the factors stay the same…..but the formulas change depending on what you’re missing.

Voltage Drop Formula (when wire size is known):

VD = K × f × I × L 1000

Where:

  • VD = voltage drop (in volts)
  • K = resistance from CEC Table D3 (ohms/km)
  • I = current (amps)
  • L = one-way length (meters)
  • f =  2 for single-phase (or use 1.73 for 3-phase)

Voltage Drop Formula (in percentage)

VD% = VD × 100 V

Example 1 – Electric Heater

We’ve got a 12 kW, 240V electric heater that’s going in a detached garage, 30 meters away from the panel in the house. The circuit runs through a raceway using #8 RW90 copper conductors.

The heater is purely resistive (so power factor is 100%), and all the equipment is labeled for a 75°C max termination temperature.

Now the big question is:
Will these wires keep the voltage drop within CEC Rule 8-102’s 3% limit for branch circuits?

And if they don’t, what’s the fix? (Spoiler: you might need to either reduce the heater size or upgrade to #6 copper.)

Given:

  • Load = 12 kW
  • Voltage = 240 V
  • Distance = 30 m
  • Power Factor = 100%
  • Wire = #8 RW90 copper in raceway
  • Equipment = 75°C rating

Step 1: Find Current (I)

Since it’s resistive (100% pf),

I = P E

I = 12,000 240

I = 50A

Step 2: Use CEC Table D3 for K

  • #8 copper, 75°C, in raceway, 100% PF
  • K = 2.54 ohms/km

Step 3: Use VD Formula

VD = K × f × I × L 1000

VD = 2.54 × 2 × 50 × 30 1000

VD = 7.62V

Step 4: Calculate Percent Drop

VD% = 7.62 × 100 240

VD% = 3.175%

Over the 3% limit.

  • Solution: try #6 AWG wire.
  • Let’s try upsizing to a #6 AWG!
  • Everything stays the same, except for the K FACTOR!

Step 5: Use CEC Table D3 for K

  • #6 copper, 75°C, in raceway, 100% PF
  • K = 1.59 ohms/km
VD = K × f × I × L 1000

VD = 1.59 × 2 × 50 × 30 1000

VD = 4.77V

Now the percentage! Remember, it has to be BELOW 3%!

Step 6: Calculate Percent Drop

VD% = 4.77V × 100 240

VD% = 1.988%

This means that we have to use a #6 AWG

UNKNOWN CONDUCTOR SIZE

K ≤ VD × 1000 I × L × F

When the conductor size is known, length is found by:

Example 2 - AC Unit

We need to find the correct conductor size to keep the voltage drop under to 3% for a single-phase 240V circuit supplying a 40-amp air conditioner that’s 21m from the panel. There is no marked Equipment termination temperature.

  • V = 240V
  • VD = 3% (Will need to do an extra calculation to turn it into Volts)
  • K = Resistance per km (from Table D3)
  • f = 2  (single-phase)
  • I = 40 A
  • L = 21m

VD= By multiplying the Applied voltage by 3% (the maximum percentage allowed by the CEC), we can find the maximum voltage drop allowed.

  • VD=240V * 0.03%
  • VD=7.2V

In order to find our Conductor size, we need to use Table D3.

So….. that K factor!

This is a VERY tricky part you need to remember!!!!

First, size the conductors at 125% [CEC Rule 8-104(3)(a) and (6)(a)] of the air conditioner load:

  • 40 x 1.25 = 50A minimum size conductors are required.
  • For equipment that is not marked with a maximum conductor termination temperature, CEC Rule 4-006 (2)(a)(i) applies; use the 60°C column of CEC Table 2.
  • Therefore, go to CEC Table 2, use No. 6 AWG copper conductors.