What is a Capacitor?
Capacitors are like electrical batteries that charge and release power super fast. They help with power factor correction, voltage stabilization, and reducing load strain.
When we size them (and their wires, breakers, and disconnects), we need to be very specific — or risk a very cranky capacitor
And cranky capacitors can explode- literally
Step 1: Calculate Capacitor Current
Use the capacitive reactance formula to figure out how much current the capacitor pulls:
That’s the Rated Current.
Step 2: Size the Conductors (CEC Rule 26-208)
To stay safe, your wires must be 135% of the rated current:
- 48A×1.35=64.8A
- Table 2 says: #6 AWG copper (good for 65A at 75°C)
Step 3: Overcurrent Protection (26-210)
You must add an O/C device (breaker or fuse) rated no more than 250% of the capacitor’s rated current:
- 48A * 2.5 = 120A
- Check Table 13 = Use **110A** (Because we can’t exceed the result!) GO DOWN!
Step 4: Disconnect Sizing (26-214)

A disconnect must be rated NOT MORE THAN 135% of the rated current:
- 140A * 1.35= 189A
- Use standard Disconnect Sizes
- 200A Disconnect
Multiple Capacitors? Let’s Add!

If you’ve got 3 capacitors pulling 48A each:
Total = 48 + 48 + 48 = 144A
Step 1
- O/C = 144A × 2.5 = 360A
- Table 13 =350A
Step 2
- Disconnect = 144A × 1.35 = 194.4A
- Use 200A disconnect
Step 3
- Conductors: 144A × 1.35 = 194.4A
- Use #3/0 AWG (good for 200A)

Taps to Multiple Capacitors?

If one large branch circuit feeds individual capacitor taps, then: -
Each tap conductor must:
- Be NOT MORE THAN 7.5 m
- Have ampacity NOT LESS THAN 1/3 of the branch circuit supplying them,
- AND meet 135% of the rated current for the capacitor it feeds
Example:
Capacitor draw = 48A (RPC) × 1.35 = 64.8A
Table 2: So each capacitor could be a #6awg
BUT:
- Main Branch Circuit is = #3/0 AWG good for 200A
- 1/3 = 66.67A
- So tap conductors must be 66.67A
- Use #4 AWG (good for 85A)
**Always go with the LARGER size**
Capacitor Review
Step 1: Use Xc = 1/2πfC and I = E/Xc
Step 2: Multiply by 1.35 to get conductor ampacity
Step 3: Multiply by 2.5 for max overcurrent device size
Step 4: Multiply by 1.35 for disconnect rating
BONUS: If using tap conductors use 7.5m max & ≥1/3 feeder size