What Is the Neutral Conductor?
The neutral conductor carries the return current in a single-phase or multi-wire circuit and helps balance current in 3-phase systems. It may or may not carry full load current — and that affects how it’s sized.
1. Is the Neutral a Current-Carrying Conductor?
Ask yourself:
- Is the neutral expected to carry current under normal operation?
- Yes? --- It must be full-sized (same as the phase conductors)
- No (e.g., balanced 3-phase loads)? --- It may be reduced
2. Use the Same Ampacity Table as for the Hot Conductors
If the neutral is current-carrying (which it often is in residential or single-phase loads), size it based on the calculated load using the appropriate ampacity table (e.g., CEC Table 2 for copper in raceways).
Example:
- If your calculated neutral load is 100A, and you're using 75°C rated conductors, you might select #3 AWG copper (from Table 2).
3. Consider Unbalanced Loads and Harmonics
- Residential: The neutral often carries almost as much current as the phase — so same size as phase conductors.
- 3-phase with nonlinear loads (like computers or VFDs): The neutral may carry more than expected due to harmonics — often it must be full size or oversized.
4. Reduced Neutral? Only When Allowed
Rule 4-018: How to Size the Neutral Conductor
Example 1: 240/120V with Two 500A Loads
Determine the maximum unbalanced load
- If loads are different, the maximum unbalanced load is the higher of the two loads
- In this case, it is 500A
Rule 4-018 Demand Factors
- ⚠️ You do not reduce the neutral or apply demand factors if:
- There is discharge lighting, and
- Anything with harmonics (fed by a 3-phase 4-wire system)
- ⚠️ You cannot touch 200A of the load
Calculation:
- 500A – 200A = 300A
- Apply 70% de-rating to anything over the 200A
- 300A * 0.7 = 210A
- Add back what we weren’t allowed to touch earlier
- 210A + 200A = 410A
- Size the neutral based on 410A
- (Rule 4-006 applies)
- Table 2 (75°C) → 600kcmil
Example 2: 240/120V with Two 500A Loads and 100A of Discharge Lighting
Calculation:
- Start with 500A
- ⚠️ Can’t touch 200A and can’t touch discharge lighting at 100A
- 500A – 200A – 100A = 200A
- Apply 70% de-rating
- 200A * 70% = 140A
- Add 200A + 100A (untouchable loads) + 140A = 440A
- Table 2 (75°C) → 700kcmil